Greystone Energy Systems - HVAC sensors and transmitters for Building Automation Management Systems

Temperature vs Resistance Charts

 

 TE200/TE500/TS/TX/

 HATS/HATX/HS/HAHS 

Code

 Typical User  Discontinued – RH Series Code
RTD’s
 
 
 02  100 ohm Platinum Honeywell, Johnson Controls  L
 12, 18, 22, 48  1000 ohm Platinum Honeywell, Siemens, Johnson Controls, Invensys, Circon  C
 13  1000 ohm Nickel Johnson Controls  M
 15  3000 ohm Platinum Honeywell  N/A
 Thermistors
 05  1801 ohm NTC TAC Vista  F
 06  3000 ohm NTC Alerton, ASI, Walker Systems  E
 07, 40  10,000 ohm NTC, Type 3 AAM, Andover, Carrier, Distech, Delta, Invensys, KMC, Reliable, Teletrol, York  D
 08  2.252 Kohm NTC Johnson Controls  G
 09  100,000 ohm NTC Siemens  H
 14  10,000 ohm NTC Type 3 w/ 11K Shunt Resistor Invensys, Solidyne  B
 20, 46  20,000 ohm NTC Honeywell  K
 24, 39, 55  10,000 ohm NTC, Type 2 Alerton, Automated Logic, Distech, Solidyne, TAC, TMS, Tekmar, Trane, Trend, Carrier  J
 59  10,000 Beta 3435K NTC Thermistor, 1% Carel